PEPPERL+FUCHS Z788.R zener barrier, part no. 071812. Channels: 2-channel, asymmetrical DC positive polarity design. Fuse rating: 50 mA. Series resistance: Terminals 1,8 max 327 Ω; terminals 4,5 max 64 Ω. Working voltage: 26.5 V / 6.5 V @ 10 µA. Built-in 250 Ω internal measuring resistor for signal measurement. Certifications: ATEX, IECEx, FM, UL, suitable for Zone 0,1,2 / Div.1,2. Protection: IP20, screw terminal wiring. Ambient temperature: -20°C ~ +60°C. Hazardous side: terminals 1-2, 3-4; Safe side: terminals 5-6, 7-8. High-power variant Z788.R.H with 80 mA fuse available.
NOTES
Model: Z788.R (071812)
Type: Asymmetrical DC zener barrier
Core difference vs Z788.R.H: Z788.R 50mA fuse; Z788.R.H high-power 80mA fuse
Core difference vs Z960: Z960 AC type; Z788.R DC positive polarity for NAMUR sensors
Must connect to qualified intrinsically safe earth