PEPPERL+FUCHS Z788 zener barrier, 12.5 × 115 × 116 mm slim modular housing. Channels: 2-channel asymmetrical DC positive polarity. Fuse: 50 mA built-in fuse. Series resistance: Terminals 1,8 max 327 Ω; terminals 4,5 max 64 Ω. Voltage rating: 26.5 V / 6.5 V @10 µA. Terminals: Hazardous side 1-2,3-4; Safe side 5-6,7-8. Protection grade: IP20, screw terminals, wire up to 2.5 mm². Certification: ATEX, IECEx, FM, UL. Operating temp: -20°C ~ +60°C. Variants: Z788 standard; Z788.R with built-in measuring resistor; Z788.H high-power 80mA fuse version. Mandatory requirement: dedicated intrinsically safe low-resistance earth connection.
NOTES
Model: Z788
Type: Asymmetrical DC positive polarity zener barrier
Core difference vs Z788.R: Z788.R with built-in measuring resistor; base Z788 without measuring resistor
Core difference vs Z960: Z960 AC barrier; Z788 DC for NAMUR sensors
Core difference vs Z788.H: Z788 50mA fuse; Z788.H high-power 80mA
ch
English