Description:
HYDAC ETS 3800 electronic temperature switch is designed for **separate external PT100 temperature probe**, the controller unit and sensing probe are split.
Measuring range: -30°C ~ +150°C
Accuracy: typical ±1.0% FS
Input: PT100 RTD (main matching HYDAC TFP100 series probe, also compatible with standard PT100 sensors)
Switching output: 1, 2 or 3 PNP outputs, max 1.2A per channel
Analog output optional: selectable 4–20mA or 0–10V
Display: 4-digit rotatable LED, °C / °F selectable
Programming: VDMA standard menu, set switch point, hysteresis, NO/NC, switching delay
Communication: IO-Link optional
Electrical connection: M12×1 connector for probe and power
Protection: IP67
No built-in probe, flexible layout for remote measurement. Widely used for hydraulic oil tank, lubrication system and industrial fluid remote temperature monitoring.
Brief comparison
ETS3200: Integrated built-in probe, tank or inline manifold installation, up to 600bar pressure resistant
ETS3800: External split PT100 probe, separate sensing head, remote measurement, matched TFP100
HTS1200: Compact OEM, fixed or programmable, no display
ETS4500: Temperature transmitter, only analog 4–20mA, no switch
Partial Models
ETS3866-2-000-000
ETS3866-3-000-000
ETS3868-5-000-000